 |
Chapter
14 - Electric Utility
ARTICLE
14-1
ARTICLE
14-2
ARTICLE
14-3
ARTICLE
14-4
ARTICLE
14-5
ARTICLE 14-1
RATES AND CHARGES
- 14-1-1
Rates
- 14-1-2
Load Restrictions
- 14-1-3
Minimum Charges
- 14-1-4
Security Lights
- 14-1-5
Special Transformers
- 14-1-6
Late Charges
- 14-1-7
Disconnect/Reconnect Charges
Section
14-1-1 Rates
-
Service Rates. Applicable to
all single and three phase residential service for individual
private premises and individually metered apartments when
all service is supplied at one point of delivery and energy
is measured through one meter. This schedule is not
applicable to resale, breakdown or standby service for customers
operating their own generating facilities.
Rate:
$ .08 per K.W.H. per month
Minimum monthly charge $4.00 per month
-
General Service Rates. This
schedule of rates is applicable to all general power and lighting
service for which no specific schedule of rates is provided
and when all energy is supplied at one point of delivery and
measured by one meter.
Rate:
$ .08 per K.W.H. per month
Minimum monthly charge $2.00 per kilowatt on
connected load
-
Temporary Service Rates. This
rate schedule is applicable to all types of light and power
service for temporary service which shall be in service for
less than one month. Applicant shall pay all costs incurred
for such installation.
Rate:
$ .15 per K.W.H. per month
Minimum monthly charge $10.00 per month
-
Irrigation Service Rates. This
rate schedule is for irrigation pumping applicable to three
phase service of ten horsepower or more.
Rate:
$ .08 per K.W.H. per month
Minimum monthly charge $10.00 per month on pumps 10
horsepower and above
$ 4.00 per month on pumps less than 10 horsepower
-
Contract and Emergency Service Rates.
Rates and conditions for such service shall be determined
by the town council.
-
State and Local Sales Taxes.
The rate schedules for purchasing electricity shall add all
applicable state and local sales taxes to each customers
bill. The sales tax shall be shown as a separate item
on the bill.
Section
14-1-2 Load Restrictions
Motors
or other services requiring more than three horsepower, or equivalent,
of operating current for single phase or more than ten horsepower,
or equivalent, of operating current for three phase, shall have
proper starting windings on equipment as approved by authorized
personnel of the town.
Section
14-1-3 Minimum Charges
The
minimum monthly charge as set forth in Section 14-1-1, subsection
A and B are based on 3 K.V.A. or less of installed transformer
capacity. When more than 3 K.V.A. of transformer is required,
the minimum monthly charge shall be increased at the rate of seventy-five
cents ($0.75) for each additional K.V.A. or fractional part thereof
required.
Section
14-1-4 Security Lights
This
section is applicable to all security lights. The customer
shall pay for the actual cost of installing the light - to include
the pole, light fixture and labor. Thereafter the town will
maintain the security light.
Rate:
$7.00 per month
Section
14-1-5 Special Transformers
This
section is for all special order transformers, transformers that
are installed for exclusive use of a customer or at the specific
request of a customer. The customer shall pay for the first
transformer and the town will stock a replacement transformer
thereafter.
Section
14-1-6 Late Charges[1]
-
A late fee of one and a half percent of the
total bill with a $5.00 minimum will be added to all electric
bills not paid by the last day of each month, unless the last
day falls on a Saturday, Sunday or a legal holiday, which
would then put the last day to make a utility payment on the
next regular working day. This penalty applies to all
commercial, irrigation and residential customers when they
are past due, regardless if they enter into a payment extension
agreement with the utility office and will continue to accrue
to an account for each month that late payments are made.
-
A person is only eligible to enter into a
payment extension agreement when they are able to show how
they will make the delinquent payments to the utility supervisor
or town manager, and it will be at their discretion and judgement
whether to allow an account to enter into a payment extension
agreement. It shall be understood that an essential
element of a payment extension agreement is that all future
electricity payments must be made by their due date in conjunction
with any delinquent payments. Should a customer not
comply with the terms of the payment extension agreement,
including becoming delinquent on future utility bills, then
the payment extension agreement shall become null and
void and this electric service subject for shut off.
Payment extension agreements are not to continue beyond three
months in any calendar year for any customer or single account.
Section
14-1-7 Disconnect/Reconnect
Charges[2]
A
disconnect/reconnect charge will be assessed for all disconnects/reconnects.
The council from time to time will review and adopt by resolution
the amount of these disconnect/reconnect charges for electric
service after it has been terminated due to nonpayment of a utility
bill or for any other valid reason caused by the customer.
ARTICLE
14-2 GENERAL PROVISIONS
- 14-2-1
Purpose
- 14-2-2
Introduction
- 14-2-3
Definitions
Section
14-2-1 Purpose
The
town hereby undertakes to comply with all lawful regulations of
the Federal Energy Regulatory Commission (FERC) codified in subpart
c of 18 CFR Part 292 dealing with arrangements with qualifying
cogeneration and small power production facilities under Section
210 of Public Utility Regulatory Policies Act of 1978 (PURPA).
Section
14-2-2 Introduction
-
The Public Utility Regulatory Policies Act
of 1978 (PURPA), under Section 210, requires the Federal Energy
Regulatory Commission (FERC) to develop rules which encourage
cogeneration and small power production. Pursuant to
Section 210, regulations have been prepared by FERC and published
in the Federal Register (45 FR 12214, February 24, 1980).
The Town of Thatcher Electric Utility ("Utility")
which is a nonregulated electric utility will implement, to
the extent possible, the procedures and requirements of FERC
Order No. 69, pursuant to these rules.
-
These rules apply to all entities willing
and able to enter into an agreement with the utility.
Provisions of these rules shall not supersede existing contracts.
Entities who have the status of "qualifying small power
production facility" and/or "qualifying cogeneration
facility" (hereinafter referred to collectively as qualifying
facility) pursuant to FERC Order No. 70 (45 FT 17959, March
20, 1980) are eligible to apply for service under these rules.
-
These rules represent general guidelines
since the nature, size and character of qualifying facilities
can vary widely. The utility reserves the right to evaluate
qualifying facilities on a case by case basis.
Section
14-2-3 Definitions
-
Terms as defined in order No. 69 (18 CFR
Part 292) shall have the same meaning for these rules unless
further defined.
-
In this chapter, unless the context otherwise
requires:
1.
"Accredited capacity" means the electrical rating
given to generating equipment that meets the utility's criteria
for uniform rating of equipment. This criteria includes
but is not limited to reliability, availability, type of equipment
and the degree of coordination between the qualifying facility
and the utility.
2.
"Capacity costs" means the costs associated with
providing the capability to deliver energy. They consist
of the capital costs of facilities used to generate and transmit
electricity or the cost to purchase such capacity from other
utilities.
3.
"Demand" means the average rate in kilowatts at
which electric capacity is made available as determined at
the point of measurement during any thirty minute period or
any other period to be determined by the utility.
4.
"Energy" means electric energy as measured in kilowatt
hours at the point of measurement.
5.
"Energy costs" means the variable costs associated
with the production of electric energy. They represent
energy related cost only or the average cost of purchased
energy. Identifiable capacity charges included in purchased
power agreements shall not be included in the calculation
of the cost of purchased energy.
6.
"Point of interconnection" means the point or points
at which the qualifying facility is to receive and/or deliver
energy or capacity and energy under normal operating conditions.
7.
"Point of measurement" means the point or points
where energy and/or demand are metered.
8.
"Present utility practice" means any of the practices,
methods and acts engaged in or approved by a significant portion
of the electrical utility industry consistent with reliability,
safety and expedition.
ARTICLE
14-3 CONDITIONS OF
SERVICE
The
conditions listed in this article shall apply to all qualifying
facilities served under these rules.
-
The utility shall purchase energy or capacity
and energy from any qualifying facility which offers to sell
energy or capacity and energy.
-
The utility shall sell any capacity and energy
that is required by the qualifying facility to the qualifying
facility. The qualifying facility shall be billed under
the applicable residential, general, industrial or contractual
service schedule.
-
The utility shall offer to provide maintenance,
interruptible, supplementary and back-up power to the qualifying
facility if requested by the qualifying facility.
-
The qualifying facility shall execute a written
agreement with the utility. The utility reserves the
right to waive this requirement. The waiving of this
requirement by the utility does not relinquish the utility's
right to require the execution of a written agreement in the
future.
-
The qualifying facility shall comply with
all requirements of the National Electrical Safety Code, American
National Standards Institute, Institute of Electrical and
Electronic Engineers, American Society of Mechanical Engineers,
and any other applicable local, state or national code and
operate its equipment according to prudent utility practice.
In case of any conflict in the foregoing codes or standards,
the utility shall decide which shall govern.
-
The utility shall interconnect and operate
in parallel with the qualifying facility. The qualifying
facility shall, to the point of interconnection, furnish,
install, operate and maintain in good order and repair and
without cost to the utility such relays, locks and seals,
breakers, automatic synchronizers and other control and protective
equipment as shall be designated by the utility as being required
as suitable for the operation of the qualifying facility in
parallel with the utility's system. The qualifying facility
shall take appropriate steps to insure that operating in parallel
will not degrade in any fashion the quality of service that
is normally maintained on the utility's system.
-
Switching equipment capable of isolating
the qualifying facility from the utility's system shall be
accessible to the utility or its agent at all times.
-
At its option, the utility or its agent may
choose to operate, without notice or liability, the switching
equipment described in subsection F of this article if, in
the opinion of the utility or its agent, continued operation
of the qualifying facility in connection with the utility's
system may create or contribute to a system emergency or safety
hazard. The utility's obligation to purchase from the
qualifying facility ceases when the utility or its agent operates
the switching equipment described in subsection F of this
article. The utility shall endeavor to minimize any
adverse effects of such operation on the qualifying facility.
-
The qualifying facility shall indemnify and
hold harmless the utility from any and all liability arising
from the operation and interconnection of the customer's facilities.
The qualifying facility shall bear full responsibility for
the installation and safe operation of the equipment required
to generate and deliver energy or capacity and energy to the
point of interconnection.
-
The utility shall provide upon request sufficient
data to allow the customer to determine the cost effectiveness
of the qualifying facility if it goes into operation pursuant
to these rules. The data given will conform to the outline
given in 292.303 (Order No. 69 - 18 CFR Part 292).
-
Any costs of interconnection which are over
and above the interconnection costs that would be incurred
due to the connection of a comparable non-generating customer
and which are incurred by the utility due to the interconnection
of the qualifying facility shall be the responsibility of
the qualifying facility. Interconnection costs may be
amortized over a period of time not greater than the length
of the contract between the utility and the qualifying facility.
-
The utility may discontinue purchase from
the qualifying facility if the utility determines that purchase
from the qualifying facility would result in costs greater
than those which the utility would incur if it did not make
such purchases.
-
The utility will give sufficient notice to
the qualifying facility when it intends to invoke subsection
L of this article.
-
The utility may discontinue sales to the
qualifying facility during a system emergency, providing that
such discontinuance is on a nondiscriminatory basis.
-
By mutual agreement between the utility and
the qualifying facility, the utility will transmit energy
or capacity and energy to another utility for purchase by
that utility. The utility shall be fairly compensated
for such transmission.
-
The qualifying facility shall provide an
advance payment to the utility if in the opinion of the utility
the costs of interconnection will be excessive or the amount
of work that must be done by the utility to provide the interconnection
facilities will be excessive.
ARTICLE
14-4 RATES FOR SALES
-
The utility shall purchase the surplus energy
or surplus capacity and energy from qualifying facilities.
The rate paid by the utility to the qualifying facility for
such surplus energy or surplus capacity and energy may be
a negotiated rate.
-
Qualifying facilities of 100 kw or less shall
be paid a standard rate, except as otherwise stated in subsection
A of this article, based on avoided cost as outlined in subsections
D and E of this article. The installation of metering
equipment shall be according to utility policy.
-
For qualifying facilities of 100 kw or more
the qualifying facility may negotiate a contract with the
utility. For qualifying facilities who choose not to
negotiate, or in the event of an impasse in negotiations between
the utility and the qualifying facility, avoided costs will
be paid. Such avoided costs shall be determined as outlined
in subsections D and E of this article except as otherwise
stated in subsection A of this article.
-
Avoided energy costs shall be estimated or
actual energy costs adjusted for the following items:
1. The
costs or savings to the utility resulting from variations
in line losses from those that would have existed in the absence
of purchase from the qualifying facility, if the utility generated
or purchased an equivalent amount of energy.
2.
Sanctions imposed for noncompliance with these rules and any
contract between the utility and the qualifying facility.
-
Capacity payments shall be made in any case
in which the qualifying facility enters into a legally enforceable
contract to provide accredited capacity. The payment
for the capacity purchase from the qualifying facility shall
take into account the following items:
1.
Length of the contract term.
2.
Reasonable scheduling of maintenance.
3.
Willingness and ability of the customer to allow the utility
to dispatch the customer's generation.
4.
The utility's ability to defer a purchase from another source
or to defer construction of a facility or a portion of a facility.
5.
Sanctions imposed for noncompliance with these rules and any
contract between the utility and the qualifying facility.
6.
Availability and reliability of the qualifying facility.
-
Any tax or payment in lieu thereof imposed
on the utility by any lawful authority on the production,
transmission, sale or purchase of energy or capacity and energy
that would not occur due to a comparable non-generating customer
shall be the responsibility of the qualifying facility.
ARTICLE
14-5 CONNECTION WITH
COGENERATION AND SMALL POWER PRODUCERS
- 14-5-1
General Provisions
- 14-5-2
Conditions of Interconnection
- 14-5-3
Interconnection
- 14-5-4
Protective Relaying
- 14-5-5
Power Factor
- 14-5-6
Metering
- 14-5-7
System Disturbances
- 14-5-8
Daily Reporting
- 14-5-9
Advance Payment
- 14-5-10
Sales to Qualifying Facilities
- 14-5-11
Rates for Purchases from Qualifying Facilities
- 14-5-12
Wheeling
- 14-5-13
Liability
Section
14-5-1 General Provisions
-
The utility shall interconnect and operate
in parallel with cogenerators and small power producers as
defined in the Federal Energy Regulatory Commission's (FERC)
regulations, 18 CFR 292. Such facilities shall be termed
"qualifying facilities".
-
The utility has the option of purchasing
the power output of such facilities or providing wheeling
service to an adjacent utility that the owner of the qualifying
facility has made prior contractual arrangements with for
receiving of such power.
-
Nothing in this article shall limit the utility's
ability to evaluate such qualifying facility and determine
terms and conditions that are mutually satisfactory to all
parties and in no way shall be detrimental to the operation
of the utility's facilities and customers.
Section 14-5-2
Conditions of Interconnection
-
The utility shall allow interconnection between
its facilities and qualifying facilities on a continuing basis
as long as the parallel operation of the qualifying facility
does not degrade, in any way, the quality of the electric
service provided to the utility's other customers. The
qualifying facility shall insure that its operation in no
way creates unsafe conditions either at its facility or on
the utility's facilities.
-
The owner of the qualifying facility shall
enter into a written agreement with the utility for interconnections,
sale or wheeling of its power prior to actual connection and
operation of its facilities.
-
The qualifying facility shall comply with
all requirements of the National Electrical Safety Code, American
National Standards Institute (ANSI), Institute of Electrical
and Electronic Engineers (IEEE), American Society of Mechanical
Engineers (ASME), the National Electric Code, General Order
95, and all local, state and federal rules and regulations
or codes which may be applicable.
Section
14-5-3 Interconnection
-
The owner of the qualifying facility shall,
to the point of interconnection, furnish, install, operate
and maintain in good repair and without cost to the utility
such relays, locks and seals, breakers, automatic synchronizers
and other control and protective equipment as shall be designated
by the utility as suitable for operations of such a facility.
-
The owner of the qualifying facility shall
provide at no cost to the utility a manually operated and
lockable, visual disconnect device that shall be for the exclusive
use of the utility and accessible by utility representatives
at all times. Usually such device will be an air switch
or fused cutouts located near the point of interconnection.
-
The protective switching equipment outlined
above in subsection B of this section may be operated without
notice or liability by the utility or utility representative
if, in the opinion of the utility or its representative, continued
operation of the qualifying facility in connection with the
utility's system may create or contribute to a system emergency
or safety hazard. The utility shall endeavor to minimize
any adverse effects of such operation on the qualifying facility.
-
Any costs of interconnection which are over
and above the interconnection costs that would be incurred
due to the connection of a comparable non-generating customer
and which are incurred by the utility due to interconnection
of the qualifying facility shall be the responsibility of
the qualifying facility.
-
The utility shall be advised of the proposed
start up and parallel time for such facilities, and a utility
representative shall be in attendance and shall approve parallel
operation.
Section 14-5-4
Protective Relaying
-
All generating units must be equipped with
short circuit interrupting devices consisting of thermal-magnetic
overcurrent devices on each phase as well as undervoltage
release and solenoid tripping accessories.
-
Over and under voltage and frequency protection
shall be provided to effectively isolate the qualifying facility
from the utility's facilities should its power output not
be within the utility's normal operating tolerances.
The normal tolerances for under and over voltage are 80% with
10 second time delay and 120% with no time delay of normal.
Under and over frequency limits are 58 Hz and 62 Hz with one
second time delay. Frequency relays are not required
for solid state inverters which are line commutated.
-
For qualifying facilities, primary, ground
fault sensing equipment shall be required to isolate the qualifying
facility from the utility's facilities unless otherwise specified
by the utility.
Section 14-5-5
Power Factor
The
power output of the qualifying facility must approach a unity
power factor when operated in parallel with the utility's facilities.
Equipment shall be installed to correct any deficiencies in power
factor by the owner of the qualifying facility at the owner's
expense.
Section 14-5-6
Metering
-
The utility shall provide metering equipment
to record all power delivered to the qualifying facility's
load during non-operation periods. Such load may consist
of not only the qualifying facility but also the customer's
load had he not installed a qualifying facility.
-
The owner of the qualifying facility shall
install metering as required by the utility's rules and regulations
to record all power produced by such facility.
-
Metering equipment for non-firm power sales
to the utility shall consist of the appropriate kilowatt-hour
meter, Q-meter, current and voltage transformers and all necessary
installation equipment. It shall also include a demand
recorder capable of producing a record of three inputs.
Such meters, recorder and related equipment shall be designated
by the utility. The owner of the qualifying facility
shall provide and dedicate to the utility such equipment and
shall be responsible for the continuing administrative costs
related to such equipment.
-
Metering equipment for non-firm power sales
to the utility shall consist of the appropriate kilowatt-hour
meter, current and voltage transformers and all necessary
installation equipment. Such metering equipment shall
be designated by the utility. The owner of the qualifying
facility shall provide and dedicate to the utility such equipment
and shall be responsible for the continuing administrative
costs related to such equipment.
-
The utility shall own and maintain all necessary
meters and associated equipment utilized for billing and monitoring
the customer's load.
Section 14-5-7
System Disturbances
Disturbances
to the utility's facilities shall be minimized to the greatest
extent possible. Such disturbances shall include but not
be limited to lagging or leading power factors, unacceptable voltage
regulation, voltage flicker and harmonics.
Section 14-5-8
Daily Reporting
-
The owner or operator of a qualifying facility
shall maintain a daily operations log for all facilities.
Such log shall contain information on unit parallel and separation
times, maintenance outages, trip operation and other unusual
events. KW operating level may also be required.
-
The utility shall have the right to periodically
review these logs.
Section
14-5-9 Advance Payment
The
qualifying facility shall pay an advance payment to the utility
for the cost of interconnection facilities.
Section 14-5-10
Sales to Qualifying Facilities
-
Power shall be provided to qualifying facilities
on a non-discriminatory basis. The qualifying facility
shall be provided service under the appropriate general service
schedule.
-
Should the qualifying facility's load also
contain other non-related loads, such load shall also be served
on the appropriate general service schedule.
-
The owner of the qualifying facility may
request electric service under a maintenance, supplementary
interruptible or backup power schedule. Should the utility
not have such a schedule in effect at the time of the request,
it may find compliance with such a request unacceptable under
Section 292.305b (2).
-
The utility may discontinue sales to the
qualifying facility during a system emergency, providing that
such discontinuance is on a nondiscriminatory basis.
Section
14-5-11 Rates for Purchases from Qualifying
Facilities
-
Rates for purchase from qualifying facilities
under 100 kw may be as designated in the utility's standard
rates for such facilities.
-
The standard rates for purchases from qualifying
facilities shall be based on the utility's "avoided costs".
The utility's avoided costs shall be determined from the current
budget year data for purchased power assuming a reduction
in the total amount of purchased power required due to qualifying
facilities.
-
Rates for qualifying facilities shall be
based on avoided costs and may be negotiated by the utility.
-
Such rates may be adjusted for the qualifying
facility's effect on the utility's system losses, administrative
costs, dispatchability, reliability, term of contract and
other factors which impact the utility's costs.
-
Should the utility's actual avoided costs
as determined in subsection B of this section drop below a
previously contracted rate, the utility retains the right
to cancel such contract and offer to renegotiate or wheel
such power from a qualifying facility. Sufficient notice
shall be provided to the owner of the qualifying facility
of use of this provision.
-
The utility shall review annually its avoided
costs as determined above and publish standard rates for purchase.
Section
14-5-12 Wheeling
-
Should the owner of a qualifying facility
request the utility to wheel its power to an adjacent utility,
the utility may do so, at its option.
-
If the utility agrees to wheel such power,
a charge may be made to the qualifying facility for interconnection
costs, any modifications to the utility's facilities to accommodate
such wheeling, use of the utility's facilities to wheel and
any associated administrative costs.
-
The amount of power wheeled may be adjusted
up or down according to the effect on the utility's system
losses due to wheeling.
Section
14-5-13 Liability
-
The qualifying facility shall defend, indemnify
and hold harmless the utility from any and all liability arising
from the operation and interconnection of the customer's facilities.
The qualifying facility shall bear full responsibility for
the installation and safe operation of the equipment required
to generate and deliver energy or capacity and energy to the
point of interconnection.
-
The owner of a qualifying facility shall
maintain worker's compensation insurance as required by law
and public liability insurance covering bodily injury and
property damage in an amount not less than $5,000,000 per
occurrence. Each public liability policy shall name
the utility as an additional insured.
-
The utility shall not be liable whether in
contract or in tort or under any other legal theory to the
owner of a qualifying facility, the owner's customers or any
other person or entity for:
1.
Lost generation revenue;
2.
Loss of use, revenue or profit;
3.
Cost of capital;
4.
Substitute use or performance; or
5.
Any other incidental, indirect, special or consequential damages.
_______________________________________________
|